Customization: | Available |
---|---|
Certification: | GB/T3906-2023 |
Voltage Level: | Medium Voltage |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Items | Parameters | |||
ModuleC | ModueF | Module V | ||
Load breakswitch | Combination unit | Vacuum circuit breaker | solating and earthing switches | |
Rated voltage | 12kV/24kV | 12kV/24kV | 12kV/24kV | 12kV/24kV |
Power frequency withstand voltage | 42kV/65kV | 42kV/65kV | 42kV/65kV | 42kV/65kV |
Lightning impulse withstand voltage | 75kV/125kV | 75kV/125kV | 75kV/125kV | 75kV/125kV |
Rated current | 630A/630A | 125A/80A | 630A/630A | 630A/630A |
Rated loaded breaking current | 630A/630A | |||
Rated cable charging breaking current | 16A/16A | 20kA | ||
5% rated loaded breaking current | 31.5A | 16A/16A | ||
Earthing fault breaking current | 200A/150A | 17.4kA | ||
Short-circuit breaking current | 31.5kA | 20kA/20kA | ||
Making capacity | 50kA/50kA | 50kA/80kA | 50kA/50kA | 50kA/50kA |
Transfer current | 1750A/1200A | |||
Short-time with standvoltage(4s) | 20kA/4s | 20kA/4s | 20kA/4s | |
Peak withstand current | 50kA/50kA | 50kA/50kA | 50kA/50kA | |
Mechanical life | 5000times | 5000times | 1000times | 5000times |